Main parameters
LM-16C glacier coolant is mainly suitable for high temperature environment. As a heat transfer fluid, the operation temperature of LM-16C is -30°C~340°C. LM-16C glacier coolant has good thermal stability and good vapor pressure due to its stable structure. LM-16C glacier coolant is recommended to use in closed cycle system. The closed-cup flash point and boiling point of LM-16C glacier coolant are 128 °C and 272 °C, respectively.
Physical parameters (reference value)
Temperature (°C) |
-30 |
-20 |
20 |
50 |
100 |
200 |
300 |
340 |
Density (g/cm3) |
1.040 |
1.034 |
1.002 |
0.985 |
0.947 |
0.872 |
0.797 |
0.767 |
Dynamic viscosity (cP) |
71.35 |
32.72 |
5.75 |
2.64 |
1.25 |
0.38 |
0.18 |
0.15 |
Thermal conductivity (W/m·K) |
0.1330 |
0.1326 |
0.1306 |
0.1314 |
0.1244 |
0.1105 |
0.0954 |
0.0884 |
Specific heat (kJ/kg·K) |
1.5379 |
1.5564 |
1.6280 |
1.7054 |
1.8422 |
1.9269 |
2.4308 |
2.6573 |

Glacier Coolant's history goes back to 1994, when the founder of Glacier Coolant,MrSongquan Bai, first invented a fluid, that can solve the problem ofmost chemicalfactoryfacing at that time, that the glycol solution they use to cool their reaction intheir processsystem, corroded the pipe and equipment seriously, This product wonfavorable commentsimmedlately once putted on the market, and was widely spread inChina. lt improved theplant operation efficiency in fine chemical factory and APlfactory.
Latterly, a series of anti-corrosion products were developed. By 2023, Glacier Coolanthasmore than 40 products covering a very wide temperature range from - 1 10°c (-166°F) to340°C (644°F), application industry expand to food and beverages, HVAc, coldstorage, datacenter, fuel cell cooling etc, The product line indudes silicon oil andthermal oil, and phasechange materials (PcM) are also developed.
Currently, the company's manufacturing facility is in Chaoyang, Liaoning, china. Wecreatedour Laboratory Seryice Unit in Beijing to improve research capabilitiesLaboratory Servicedivision helps the customer to design the product that can meettheir specific requirementand solve the technique problems they are encounteringThe center can also provide sample